Publication 1746-UM006B-EN-P - August 2005

4-36 Configuration and Programming

Output Data File Word -
Sequencer Mode

The Output Data File is only one word in size. Appendix E contains
worksheets for Sequencer Mode operation.

O:e.0 Direct Outputs (Dynamic)

O:e.0 Bits 0 through 7 - Direct Outputs

These bits are used for direct user program control of the outputs. Bits
0, 1, 2, and 3 represent the four Physical Outputs of the module.
When one of these bits is set, the corresponding output circuit is ON if
that output is under user program control (refer to M0:e.0 Output
Source Select
on page 4-3).

Bits 4, 5, 6, and 7 represent Soft Outputs which are not physically
connected to output circuits, but are the same in all other respects.

O:e.0 Bits 8 through 15

Bits 8 through 15 are reserved and must be reset to 0.

If your user program will not be using the Direct Outputs field, you
can improve system throughput by setting the Scanned Output Words
to 0.

Direct Outputs (bits 0-7)

Output Response

0

Corresponding output is OFF

1

Corresponding output is ON

R R R R R

R

Direct Outputs, Word 0

Bit Number (decimal)

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

O:e.0

Direct Outputs

R R

Reserved

Direct user

program control of

Soft Outputs

Direct user

program control of

Physical Outputs