Mixing rack-optimized and direct connections, Chapter summary – Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual

Page 15

Advertising
background image

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

7

About the Adapters Chapter 1

eight I/O modules. If you use a rack-optimized connection to transfer the data,
you only need a single connection – the connection to the I/O adapter.

See the EtherNet/IP Design Considerations Reference Manual,
publication

ENET-RM002

for more information on connections.

Mixing Rack-optimized and Direct Connections

You can mix communication formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter. I/O modules
configured for direct communication communicate at their own individual RPIs
and ignore the rack-optimized RPI.

Chapter Summary

In this chapter, you were introduced to the features of the POINT I/O and
ArmorPOINT I/O Adapters, and considerations for installation and usage.

IMPORTANT

Although rack-optimized connections offer an efficient way to use
resources, there are a few limitations on their use:

• You can use only rack-optimized connections to send data to and

from digital I/O modules. Analog or speciality I/O requires direct
connections.

• All data is sent at the same time as the RPI rate of the I/O adapters.

If the update rate required for a digital module is different from the
RPI of the rack-optimized connection, a direct connection to that
digital I/O module is required.

Advertising