Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual

Page 83

Advertising
background image

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

75

EtherNet/IP I/O Adapter Specifications Appendix A

Environmental Specifications

Specification

Description

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F) – 1734-AENTR
-20…60 °C (-4…140 °F) – 1738-AENTR

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40…85 °C (–40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Group 1, Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges – 1734-AENTR
8 kV contact discharges
8 kV air discharges

Radiated RF immunity

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz – 1734-
AENTR

EFT/B immunity

IEC 61000-4-4:
±4 kV at 5 kHz on power ports
±2 kV at 5 kHz on communication ports
±3 kV at 5 kHz on communication ports – 1734-AENTR

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on unshielded communications ports (tested as
balanced circuits)

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Advertising