Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual

Page 77

Advertising
background image

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

69

Troubleshoot the Adapter Chapter 6

Network activity

Off

No link established with Port 1 or Port 2.

Green

Link established with Port 1 and/or Port 2 at 100 Mbps.
Link established with Port 1 and Port 2.
One port at 100 Mbps and one port at 10 Mbps

Flashing green

Transmit or receive activity present on Port 1 and/or Port 2 at 100 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2.
One port at 100 Mbps and one port at 10 Mbps.

Yellow

Link established with Port 1 and/or Port 2 at 10 Mbps.

Flashing yellow

Transmit or receive activity present Port 1 and/or Port 2 at 10 Mbps.

Network status

Off

Device not initialized. Device does not have an IP address.

Green

CIP connections present. Device online and has an IP address, and CIP connections
are established.

Flashing green

No CIP connections present. Device has an IP address, but no CIP connections are
established.

Flashing red/green

Device is in self-test.

Flashing red

One or more CIP connections have timed out.

System power

Off

Not active; adapter power is off, or DC-DC converter problem is present.

Green

System power is on; DC-DC converter output is active (5V).

Adapter power

Off

Not active; adapter power is off

Green

Power is on; 24V input is present.

POINTBus status

Off

Device is not online.
- Device has not completed Dup_MAC_ID test.
- Device not powered - check Adapter Status indicator

Green

Device is online and has connections in the established state.

Flashing green

Device is online but has no connections in the established state.
Firmware (NVS) update in progress.

Flashing red/green

LED cycle power test present.

Flashing red

Communication faulted device - the device has detected a network access error
and is in communication faulted state.
Device has received and accepted an Identify Communication Faulted Request -
long protocol message

Red

Unrecoverable fault has occurred:
- POINTBus is off.

Link 1 or Link 2 activity/status

Off

No link established.

Green

Link established at 100 Mbps

Flashing green

Transmit or receive activity present at 100 Mbps.

Yellow

Link established at 10 Mbps.

Flashing yellow

Transmit or receive activity present at 10 Mbps.

Status Indicators for 1738-AENTR Adapter

Status

Description

Advertising