Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

21

Configure the Adapter for Your EtherNet/IP Network Chapter 3

Set the

Network Address

The adapters ship DHCP-enabled and with the switches set to 999. To change
the network address, do the following.

Set the Network Address for POINT I/O Adapter

Use the thumbwheel switches located on the adapter. Press either the + or -
buttons to change the number.

Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.

Retrieve the IP address from non-volatile memory.

The adapter reads the thumbwheel switches first to determine if the switches are
set to a valid number. You set the node address by using the 3-position
thumbwheel switch. Press the + or - buttons to change the number. Valid settings
range from

001…254.

When you use the thumbwheel to assign an address and set it to

001, the adapter

gateway address is set to

0.0.0.0. and the subnet mask is 255.255.255.0 . When

you use the thumbwheel to assign an address and set it between

002...254, the

adapter gateway address is set to

192.168.1.1.

The adapter does not have a host name assigned, or use any Domain Name
System when using the thumbwheel settings.

If DHCP is not enabled, the adapter uses the IP address, along with other TCP
configurable parameters, stored in non-volatile memory.

44848

Network address thumbwheel
Press either the + or - buttons
to change the number and
assign the IP address.

0 2

0

1734-AENTR

Module
Status

Network
Activity

Network
Status

Point Bus
Status

System
Power

Field
Power

POINT I O

Link 1
Activity/
Status

Link 2
Activity/
Status

IP ADDRESS

Advertising