Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5

The

New Module dialog opens.

4. Click Change... and then enter values for Name and Slot, noting we used

the following values.

5. Note that the requested packet interval (RPI) is the same as was chosen by

the adapter. You use this value for the rack-optimized connection to the I/
O modules.

6. Click OK to accept the configuration.

The name of the OW2 appears indented under the local 1734-AENTR in
the I/O Configuration folder.

Name

POINT_Relay_Output

Slot

1

IMPORTANT

To avoid overloading the adapter, we recommend that you set RPI no
less than 10 ms for rack connections and 50 ms for direct connections.