Download the program to the controller – Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual
Page 68
60
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
7. From the New Module dialog, click the Connection tab.
The New Module dialog opens.
8. From the New Module dialog, enter 50 for the Requested Packet Interval
(RPI).
9. Keep the following unchecked.
a. Inhibit Module
b. Major Fault on Controller If Connection fails While in Run Mode
10. Click OK.
11. Choose File
→
Save and enter the name and location of the file.
Download the Program to
the Controller
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1. From the main menu, choose Communications>Who Active.
2. From the Who Active dialog, navigate to select the slot where the
controller is located in the chassis.