60

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

7. From the New Module dialog, click the Connection tab.

The New Module dialog opens.

8. From the New Module dialog, enter 50 for the Requested Packet Interval

(RPI).

9. Keep the following unchecked.

a. Inhibit Module

b. Major Fault on Controller If Connection fails While in Run Mode

10. Click OK.
11. Choose File

Save and enter the name and location of the file.

Download the Program to
the Controller

Follow this procedure to download the program we just saved to the
ControlLogix controller.

1. From the main menu, choose Communications>Who Active.
2. From the Who Active dialog, navigate to select the slot where the

controller is located in the chassis.