Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual
Page 74
66
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter 6 Troubleshoot the Adapter
Status Indicators for 1734-AENTR Adapter
Status
Description
Module status
Off
No power applied to device
Solid green
Device operating normally
Flashing red/green
Module self-test
Flashing red
Recoverable fault.
Complete firmware update, verify address switches.
Solid red
Unrecoverable fault, may require device replacement.
Network status
Off
Device is not online
- Device has not completed Dup_MAC_ID test.
- Device not powered - check module status indicator.
Flashing green
Device is online but has no CIP connections in the established state.
Solid green
Device online and has CIP connections in the established state.
Flashing red
One or more CIP connections in timed-out state.
Check for I/O module failure and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing red/green
Module self-test
Network Activity
Off
No link established with Port 1 or Port 2.
Solid green
Link established with Port 1 and/or Port 2 @ 100 Mbps.
Link established with Port 1 and Port 2.
One port @ 100 Mbps and the other port @ 10 Mbps.
Flashing green
Transmit or receive activity present on Port 1 and/or Port 2 @ 100 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2.
One port @ 100 Mbps and the other port @ 10 Mbps.
Solid yellow
Link established with Port 1 and/or Port 2 @ 10 Mbps.
Flashing yellow
Transmit or receive activity present on Port 1 and/or Port 2 @ 10 Mbps.
Link 1 or Link 2 Activity /
Status
Off
No link established.
Solid green
Link established @ 100 Mbps.
Flashing green
Transmit or receive activity present on indicated port @ 100 Mbps.
Solid yellow
Link established @ 10 Mbps.
Flashing yellow
Transmit or receive activity present on indicated port @ 10 Mbps.
POINTBus status
Off
Device is not online.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Flashing green
Device is online but has no connections in the established state.
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established.
Flashing red
Recoverable fault occurred:
• At cycle power, the number of expected modules does not equal
the number of modules present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred - POINTBus is off.
Flashing red/green
LED powerup test is in progress.