Configure the Adapter for Direct Connection in RSLogix 5000 Software Chapter 4

The New Module dialog opens.

4. Enter values for Name and Slot, noting that we used the following values.

5. Choose Connection.

The RPI is selectable since it is a direct connection.

6. Enter 50 for requested packet interval (RPI) to set how often you exchange

data with the I/O adapters.

7. Click OK to save the configuration.

The relay output module appears under Ethernet.

Name

POINT_Relay_Output

Slot

1

IMPORTANT

To avoid overloading the I/O adapters, we recommend that RPI be no
less than 10 ms for rack connections and 50 ms for direct
connections.