Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

47

Chapter

5

Configure the Adapter for Direct Connection
and Rack Optimization in RSLogix 5000
Software

Overview

This chapter guides you through the steps required to configure your AENTR
adapter with both direct and rack-optimized I/O connections using
RSLogix 5000 software.

You can mix I/O connection formats for different I/O modules communicating
through the same adapter. I/O modules set up to use rack optimization
communicate at the rate of the RPI configured for the adapter.

I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimized I/O connection has no bearing on the direct
I/O connections. The modules presented in this chapter have a configuration
using RSLogix 5000 software, revision 11. The chapter contains the following
main sections

.

Topic

Page

Set Up the Hardware

48

Create the Example Application

49

Configure the I/O Modules

50

Add the Local EtherNet/IP Bridge to the I/O Configuration

50

Add the I/O Adapter to the I/O Configuration

52

Add the POINT I/O Module and Configure for Rack-optimized Connection

56

Add the POINT I/O Module and Configure For Direct Connection

58

Download the Program to the Controller

60

Verify the Module Chassis Size

61

Access Module Data

64

ATTENTION: You must use series C POINT I/O modules with the
adapter. Series A or B POINT I/O modules do not work with the adapter.