A – ethernet/ip i/o adapter specifications, Specifications, Ethernet/ip i/o adapter specifications – Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual

Page 79: Appendix

Advertising
background image

Rockwell Automation Publication 1734-UM014B-EN-P - June 2013

71

Appendix

A

EtherNet/IP I/O Adapter Specifications

Specifications

Following are specifications for the POINT I/O and ArmorPOINT I/O
modules

General Specifications – POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP
Adapters 1734-AENTR, 1738-AENTR

Specification

Description

Module location

Starter module - left side of the 1734 system

LED Indicators

Adapter status - green/red
Network status - green/red
POINTBus status - green/red
Network activity - green
System power (POINTBus 5V power) - green
Field power (24V from field supply) - green
Link activity status - green/yellow

Input voltage ratings, nom

24V DC

Input voltage range

10…28.8V DC

Inrush current, max

6 A for 10 ms

Power consumption, max

10.4 W @ 28.8V DC

Power dissipation, max

6.3 W @ 28.8V DC

Thermal dissipation, max

21.5 BTU/hr. @ 28.8V DC

POINTBus output current,
max

0.8 A @ 5V DC ± 5% (4.75…5.25)

Input overvoltage protection

Reverse polarity protected

Isolation voltage

50V (continuous), Basic Insulation Type
Tested at 1250V rms for 60s

Field side power, max

24V DC (+ 20% = 28.8V DC) @ 400 mA

Fieldbus power current, max

10 A

Fieldbus power range

10…28.8V DC

Interruption

Output voltage will stay within specifications when input drops out
for 10 ms at 10V with maximum load

Wiring category

(1)

(1) Use this conductor category information for planning conductor routing. Refer to publication

1770-IN041

,

Industrial Automation Wiring and Grounding Guidelines.

1 – on power ports
2 – on communications ports

Advertising