EtherNet/IP I/O Adapter Specifications
Specifications
Following are specifications for the POINT I/O and ArmorPOINT I/O
modules
General Specifications – POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP
Adapters 1734-AENTR, 1738-AENTR
Specification
Description
Module location
Starter module - left side of the 1734 system
LED Indicators
Adapter status - green/red
Network status - green/red
POINTBus status - green/red
Network activity - green
System power (POINTBus 5V power) - green
Field power (24V from field supply) - green
Link activity status - green/yellow
Input voltage ratings, nom
24V DC
Input voltage range
10…28.8V DC
Inrush current, max
6 A for 10 ms
Power consumption, max
10.4 W @ 28.8V DC
Power dissipation, max
6.3 W @ 28.8V DC
Thermal dissipation, max
21.5 BTU/hr. @ 28.8V DC
POINTBus output current,
max
0.8 A @ 5V DC ± 5% (4.75…5.25)
Input overvoltage protection
Reverse polarity protected
Isolation voltage
50V (continuous), Basic Insulation Type
Tested at 1250V rms for 60s
Field side power, max
24V DC (+ 20% = 28.8V DC) @ 400 mA
Fieldbus power current, max
10 A
Fieldbus power range
10…28.8V DC
Interruption
Output voltage will stay within specifications when input drops out
for 10 ms at 10V with maximum load
Wiring category
(1)
(1) Use this conductor category information for planning conductor routing. Refer to publication
,
Industrial Automation Wiring and Grounding Guidelines.
1 – on power ports
2 – on communications ports