Rockwell Automation 1738-AENTR, Series A 1734 POINT I/O and 1738 ArmorPOINT I/O 2 Port Ethernet/IP Adapter User Manual User Manual
Page 20
12
Rockwell Automation Publication 1734-UM014B-EN-P - June 2013
Chapter 2 Install Your Adapter
5. Slide the safety end cap up to remove it, exposing the backplane and power
interconnections.
Mount the ArmorPOINT I/O Adapter and Base on a Wall or Panel
To mount the ArmorPOINT I/O adapter on a wall or panel, use the screw holes
provided in the adapter module
.
Refer to the drilling dimensions illustration for the ArmorPOINT I/O adapter
with I/O bases to guide you in mounting the adapter and I/O bases.
Drilling Dimensions
Install the mounting base as follows:
1. Lay out the required points as shown in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
3. Mount the adapter using #8 (M4) screws.
4. Ground the system using the ground lug connection in the I/O base. The
ground lug connection is also a mounting hole.
5. Mount the terminating base that was shipped with the adapter as the last
base in the backplane instead of the base that was shipped with the
I/O module.
6. Set the network address thumbwheel switches to the desired value. See
in chapter
for more information on setting the IP
address.
WARNING: If you connect or disconnect the Ethernet cable with power
applied to this module or any device on the network, an electrical arc
can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
IMPORTANT
The ArmorPOINT I/O adapter must be mounted on a grounded
metal mounting plate or other conductive surface.
46.25mm
(1.82in)
56.00mm
(2.20in)
102.0mm
(4.01in)
51.90mm
(2.04in)
20.10mm
(0.79in)
51.90mm
(2.04in)
51.90mm
(2.04in)
20.10mm
(0.79in)
45175