The following describes the status indicators on the 1738-AENTR.

This module has the following indicators:

Adapter, Network, and POINTBus status indicators for
EtherNet/IP

Adapter and System power indicators

Network activity indicator

1738-AENTR

EtherNet I/P

Adapter
Status

Network
Activity

Network
Status

PointBus
Status

System
Power

Adapter
Power

conformance tested

PWR

IP ADDRESS

Link 2
Activity/
Status

Link 1
Activity/
Status

44830

Link 1 activity/status indicator

Link 2 activity/status indicator

Adapter status indicator
Network activity indicator
Network status indicator

System power indicator
Adapter power indicator

POINTBus status indicator

Status Indicators for 1738-AENTR Adapter

Status

Description

Adapter status

Off

No power applied to device

Green

Device operating normally

Flashing red/green

Device is in self-test

Flashing red

Recoverable fault.
-Firmware (NVS) update.
-Address switches changed.

Red

Unrecoverable fault
-Self-test failure (Flash checksum failure at power up,
RAM test failure or EEPRO< checksum failure at cycle power).
-Firmware fatal error.