Logix5000 controller combinations, Connections to panelview terminals – Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 8 Communicate with PanelView Terminals

Logix5000 Controller Combinations

Your controller type determines which communication module to use.

You must complete these tasks before your controller can communicate with
PanelView terminals over an EtherNet/IP network:

Set the IP addresses for the controller’s EtherNet/IP communication

module and the HMI terminal.

Connect all wiring and cabling.

Connections to PanelView
Terminals

To establish communication between a PanelView or PanelView Plus terminal,
specify controller connections.

Table 21 - Choosing a Communication Module

Controllers

Communication Modules

ControlLogix

1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-
EN2TXT, 1756-EN3TR, or
1756-EN2TSC communication modules

1768 CompactLogix

1768-ENBT communication module

1769-L23E-Q1B, 1769-L23E-QBFC1B, 1769-L32E, or 1769-
L35E CompactLogix

A built-in EtherNet/IP port

PowerFlex 700S with DriveLogix

1788-ENBT EtherNet/IP communication module

Table 22 - PanelView Terminal Connections

Type of Communication

Terminal Type

PanelView

PanelView Plus

Implicit (connected)

Logix controller communicates to the PanelView terminal like

an I/O module.

You must add the PanelView terminal to the I/O configuration

tree for the controller project.

Supported

Not supported

Explicit (unconnected)

Communication is set up in PanelBuilder or RSView ME

software.

All communication is initiated by the PanelView or PanelView

Plus terminal.

Supported

Supported