Chapter 6 Interlocking and Data Transfer between Controllers

5. If the target module is configured in the I/O Configuration folder of the

originating controller, click Browse to select the module or manually type
the path to the target module.

A manually typed path begins with the name of the local EtherNet/IP
communication module, the port the message exits (2 for EtherNet/IP),
and the IP address of the next module in the path, which could be the
target module.

EXAMPLE

Communication path from a Logix5000 controller to a Logix5000 controller over
an EtherNet/IP network

washer, 2, 168.127.127.12, 1, 0

Ethernet Network

55
75

E

N

2T

55
75

E

N

2T

IP Address
168.127.127.12

Message

Where

Indicates

Washer

Name of the 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR,
1756-EN2TXT, or 1756-EN3TR module

2

Ethernet port of the 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-
EN2TR, 1756-EN2TXT, or 1756-EN3TR module

168.127.127.12

IP address of the 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR,
1756-EN2TXT, or 1756-EN3TR Module in the destination chassis

1

Backplane port of the 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-
EN2TR, 1756-EN2TXT, or 1756-EN3TR Module in the destination
chassis

0

Slot number of the destination controller