Ring statistics web page – Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 9 Diagnostic Web Pages

Ring Statistics Web Page

The Ring Statistics web page provides a summary of the module’s operating state
in a DLR application.

The most commonly monitored fields are circled in the graphic and described in
the table that follows.

This table describes the field most commonly used on the Ring Statistics
web page.

IMPORTANT

The Ring Statistics web page, and the descriptions in this section, only apply to

modules you can use in a Device-level Ring (DLR) network:

1756-EN2TR communication module
1756-EN3TR communication module

Table 26 - Ring Statistics Web Page

Field

Specifies

Ring Supervisor

Ring Supervisor Mode

Whether a module is configured to function as supervisor node or a ring node.

Ring Supervisor Status

Whether a module that is configured to function as a supervisor node is functioning as the active ring supervisor or a backup

supervisor node.

Ring Fault Location

Last Active Node on Port 1

The IP or MAC ID address of the last active node between port 1 on the module and the faulted part of the network.

Last Active Node on Port 2

The IP or MAC ID address of the last active node between port 2 on the module and the faulted part of the network.

Active Ring Supervisor

Address

The IP or MAC ID address of the active ring supervisor.

Precedence

The precedence value of the module. If the active supervisor node’s operation is interrupted the backup supervisor with the next

highest precedence value becomes the active supervisor node.