Construct the physical network – Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 36

Advertising
background image

36

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 4 Configure a Supervisor on a Device-level Ring Network

Construct the Physical
Network

The first thing you must do to create a new DLR network is physically connect
all necessary devices to the network. However, leave at least one connection
unmade, that is, temporarily omit the physical connection between two nodes on
the ring, as the factory default settings of DLR devices are set to operate in linear/
star mode or as ring nodes on existing DLR networks.

This figure shows an example of a new DLR network with one physical
connection left open.

Figure 4 - Example Device-level Ring Topology with One Connection Left Unmade

Comm Adapter

MOD

NET

LINK 1

LINK 2

X 100

X 10

X 1

LINK 1

LINK 2

Last physical
connection is not
made.

Advertising