Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages Chapter 10

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

129

Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages Chapter 10

Troubleshoot the
1756-EN2TR Communication
Module

Use this table to determine what diagnostic web page to use when you
troubleshoot issues on your module.

Table 33 - Required Diagnostic Web Pages

Technical Issue

Diagnostic Web Page

CPU utilization

Diagnostic Overview

CIP connection statistics

TCP connections

HMI/MSG statistics

I/O and produce/consume packets per second

I/O and produce/consume packet counts

Link status

Ethernet Statistics

Speed

Duplex

Autonegotiate status

Ethernet errors

Connections closed due to a Timeout

Choose this path to tab:
Diagnostics>Advanced Diagnostics>Miscellaneous>System
Data>Connection Manager Cmd Object Info

Network topology

Ring Statistics

Network status

Ring supervisor statistics

Ring supervisor IP address or MAC ID

IMPORTANT

The 1756-EN2TR communication module has two ports. Some diagnostics are

tracked for Port 1 and Port 2 because the values may be different between
ports.