Chapter 6 Interlocking and Data Transfer between Controllers

Receive MSGs from PLC-5 or SLC 500 Controllers

To receive MSGs from PLC-5 or SLC 500 processors, follow these steps.

1. If the originating controller is a PLC-5 or SLC 500 processor, in the MSG

instruction, select PLC5.

2. On the MultiHop tab, specify the following:

IP address of the EtherNet/IP communication module that is local to

the Logix5000 controller

Slot number of the Logix5000 controller

If the controller is a

For this section

And this item

Specify

PLC-5

This PLC-5

Communication Command

PLC-5 Typed Read or PLC-5 Typed Write

Data Table Address

Starting address of the data in the PLC-5 controller

Size in Elements

Number of elements to read or write

Port Number

2

Target Device

Data Table Address

Type, in quotation marks [“ “], the name of the tag in the ControlLogix

controller (for example, “count”).

MultiHop

Select Yes.

SLC 500

This Controller

Communication Command

PLC5 Read or PLC5 Write

Data Table Address

Starting address of the data in the SLC 500 controller

Size in Elements

Number of elements to read or write

Channel

1

Target Device

Data Table Address

Type, in quotation marks [“ “], the name of the tag in the ControlLogix

controller (for example, “count”).

MultiHop

Select Yes