Chapter 10 Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages

130

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 10 Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages

Diagnostic Overview Statistics

The Diagnostic Overview web page presents a summary of the current
configuration and overall status of the module.

1. Review the Module Resource Utilization table to monitor your

CPU utilization.

2. Review the CIP Connection Statistics (All Ports) table to monitor CIP

connection usage.

If the CPU
utilization rate is

Then

0...80%

No action is required.
Important: This is the optimal rate.

Greater than 80%

Take steps to reduce your CPU utilization. See Internet Group Multicast Protocol on

page 144

.

Adjust your connection’s requested packet interval (RPI).

Reduce the number of devices connected to your module.
Important: Your EtherNet/IP communication module can function at 100% CPU capacity,
but at or near this rate, you run the risk of CPU saturation and performance problems.