Send Email Chapter 7

3. Click the Communication tab.

4. In the Path field, type the path from the controller to the EtherNet/IP

communication module.

The path starts with the controller initiating the MSG instruction. The
second number in the path represents the port from which the message
exits and the address of the next module in the path.

For example, if the EtherNet/IP communication module is in the same
chassis as the controller and is in slot 2, the path is: 1, 2.

5. If all the devices in the path are configured in the initiating controller’s I/O

Configuration tree, click Browse to select the target module.

The software automatically fills in the path.

6. Click OK.

For more information on configuring the path of an MSG instruction, see the
Logix5000 Controllers General Instructions Reference Manual, publication

1756-RM003

.