Chapter 6 Interlocking and Data Transfer between Controllers

Connections for Messages

Messages transfer data to other modules, such as other controllers or operator
interfaces. Each message uses one connection, regardless of how many modules
are in the message path. To conserve connections, you can configure one message
to read from or write to multiple modules.

These connected messages can leave the connection open (cache) or close the
connection when the message is done transmitting.

Cache Message Connections

Use the message’s execution rate to determine whether to cache a connection
or not.

Table 15 - Message Connections

Type of Message

Communication Method Used

Connection Used

CIP data table read or write

CIP

Yes

PLC-2, PLC-3, PLC-5, or SLC (all types)

CIP

No

CIP with Source ID

No

DH+

Yes

CIP generic

CIP

Your choice

(1)

(1) You can connect CIP generic messages, but for most applications we recommend you leave CIP generic messages unconnected.

Block-transfer read or write

Yes

Table 16 - Guidelines for Caching Message Connections

Message Execution

Instruction Configuration

Repeated

Cache the connection.

Important: Caching keeps the connection open and optimizes execution time.
Opening a connection each time the message executes increases execution time.

Infrequent

Do not cache the connection.

Important: Not caching closes the connection upon completion of the message,
freeing up the connection for other uses.