Chapter 10 Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages

142

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 10 Troubleshoot an EtherNet/IP Communication Module with Diagnostic Web Pages

2. Review the values in the Media Counters Port 1 table.

If

Then

Any media counters are greater than zero

You need to investigate further.

These errors are counted:

Alignment
FCS
Carrier Sense

A duplex mismatch exists between your EtherNet/IP communication module and the switch port.

To clear the duplex mismatch:

1. Configure the EtherNet/IP communication module and the corresponding Ethernet switch port for a forced operation, not

autonegotiation.

2. Verify that the firmware revision of your Logix controller and switch or converter are identical.
3. If the revisions are not identical, replace the controller, switch or converter so that they match.

Single Collisions or Multiple Collisions are greater than
zero

No action is required.
Important: If two stations attempt to transmit data simultaneously, the packets collide with each other. However, collisions
are not errors and do not indicate a network problem. The number of network collisions can vary greatly due to traffic
patterns or CPU utilization. Consequently, there is no set range of acceptable collisions for each outgoing packet. Collisions
are a normal aspect of Ethernet networking.

Late Collisions are greater than zero

1. Check to see if a network segment is too long.
2. Remove repeaters from between devices.

Excessive Collisions are greater than zero

Calculate your network’s typical rate of excessive collisions and decide whether the rate of packet loss will affect your
network’s performance.
Important: Excessive collisions indicate that your network has become congested. For each collision after the sixteenth,
your network drops a packet.

MAC Transit Errors are greater than zero

No action is required.

Frame Too Long is greater than zero

Limit the size of your tags to

 500 bytes.