Duplicate ip address detection – Rockwell Automation 1734-AENTR EtherNet/IP Network Configuration User Manual User Manual

Page 29

Advertising
background image

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

29

Configure an EtherNet/IP Communication Module to Operate on the Network Chapter 3

Reset the Module IP Address to Factory Default Value

You can reset the module’s IP address to its factory default value with the
following methods:

If the module has rotary switches, set the switches to 888 and cycle power.

If the module does not have rotary switches, use a MSG instruction to the

reset the IP address.

Duplicate IP Address
Detection

Some EtherNet/IP communication modules support duplicate IP
address detection. The module verifies that its IP address does not match any
other network device’s IP address when you perform either of these tasks:

Connect the module to a EtherNet/IP network.

Change the module’s IP address.

If the module’s IP address matches that of another device on the network, the
module’s EtherNet/IP port transitions to Conflict mode. In Conflict mode, these
conditions exist:

OK status indicator is blinking red.

Network (NET) status indicator is solid red.

On some EtherNet/IP communication modules, the module status display

indicates the conflict.

The display scrolls:OK <IP_address_of_this_module> Duplicate IP
<Mac_address_of_duplicate_node_detected>

For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4

On some EtherNet/IP communication modules, the module’s diagnostic

webpage displays information about duplicate IP address detection.

For more information on which EtherNet/IP communication modules
support displaying duplicate IP address on their diagnostic webpage, see
the Technical Note titled Logix modules Duplicate IP address detection
enhancement
, #118216, in the Technical Support Knowledgebase
available at

http://www.rockwellautomation.com/knowledgebase/

.

Advertising