Configure an EtherNet/IP Communication Module to Operate on the Network Chapter 3

7. Configure the port settings.

8. Click OK.

To

Then

Use the default port speed and
duplex settings

Leave Auto-negotiate port speed and duplex checked.

This setting determines the actual speed and duplex setting.

Manually configure your port’s
speed and duplex settings

Follow these steps.

1. Clear the Auto-negotiate port speed and duplex checkbox.
2. From the Current Port Speed pull-down menu, choose a port

speed.

3. From the Current Duplex pull-down menu, choose the appropriate

Duplex value, that is, Half Duplex or Full Duplex.

IMPORTANT

Consider the following when you configure the module’s port settings:

If the module is connected to an unmanaged switch, leave Auto-

negotiate port speed and duplex checked or the module will fail.

If you are forcing the port speed and duplex with a managed

switch, the corresponding port of the managed switch must be
forced to the same settings or the module will fail.