80

Rockwell Automation Publication ENET-UM001L-EN-P - March 2014

Chapter 6 Interlocking and Data Transfer between Controllers

Configure a MSG to an SLC 500 Controller

Configure a MSG to a PLC-5 Controller

3. Click the Communication tab.

4. In the Path field, type the communication path.

If the data is

And you want to

For this item

Type or choose

Integer

Read (receive) data

Message Type

SLC Typed Read

Source Element

Data table address in the SLC 500 controller (for example, N7:10)

Number of Elements

Number of integers to transfer

Destination Tag

First element of int_buffer

Write (send) data

Message Type

SLC Typed Write

Source Tag

First Element of int_buffer

Number of Elements

Number of integers to transfer

Destination Element

Data table address in the SLC 500 controller (for example, N7:10)

Floating-point (REAL)

Read (receive) data

Message Type

SLC Typed Read

Source Element

Data table address in the SLC 500 controller (for example, F8:0)

Number of Elements

Number of values to transfer

Destination Tag

First element of the tag (controller-scoped) in this controller for the data

Write (send) data

Message Type

SLC Typed Write

Source Tag

First element of the tag (controller-scoped) in this controller that contains the data

Number of Elements

Number of values to transfer

Destination Element

Data table address in the SLC 500 controller (for example, F8:0)

If the data is

And you want to

For this item

Type or choose

Integer

Read (receive) data

Message Type

PLC5 Typed Read

Source Element

Data table address in the PLC-5 controller (for example, N7:10)

Number of Elements

Number of integers to transfer

Destination Tag

First element of int_buffer

Write (send) data

Message Type

PLC5 Typed Write

Source Tag

First element of int_buffer

Number of Elements

Number of integers to transfer

Destination Element

Data Table address in the PLC-5 controller (for example, N7:10)

Floating-point (REAL)

Read (receive) data

Message Type

PLC5 Typed Read

Source Element

Data table address in the PLC-5 controller (for example, F8:0)

Number of Elements

Number of values to transfer

Destination Tag

First element of the tag (controller-scoped) in this controller for the data

Write (send) data

Message Type

PLC5 Typed Write

Source Tag

First element of the tag (controller-scoped) in this controller that contains the data

Number of Elements

Number of values to transfer

Destination Element

Data table address in the PLC-5 controller (for example, F8:0)