Rice Lake iQUBE2 Digital Diagnostic Junction Box User Manual

Page 50

Advertising
background image

46

iQUBE

2

Installation Manual

See Section 6.0 on page 46 for more information about the commands listed in Table 5-11.

Command

n = digital I/O bit number

Description

Values

DIGIOn

Set digital I/O bit function

OFF, ZERO, TARE, NT/GRS, UNITS, PRINT, CLRCN,
CLRTAR, SETPNT, CELHLTH, HOSTCTL

DIGIOn.SCALE

Assign digital I/O bit n to scale

1–5 (scale number)

DIN#0

Read all digital inputs

Returns value 0–F (status of bits 1–4 represented as
hexadecimal values 1, 2, 4, 8)

DIN#n

Read digital input n

1=low, 0=high

DON#0

Set all digital outputs on (active)

DON#n

Set digital output n on

1–4

DOFF#0

Set all digital outputs off (inactive)

DOFF#n

Set digital output n off

1–4

MSDOUT

Reads all outputs in the system

Table 5-10.

iQUBE

2

Digital I/O Commands

Command

s = scale number

Description

Values

DIA.PS

Query power supply error

DIA.MSCONNECT

Query secondary connection error

DIA.PSEXC

Query excitation error

DIA.CELLCONNECT

Query cell connection error

DIA.FLAGS

Show all diagnostic flags simultaneously

See Section 6.2.4 on page 50

DIA.CLEAR

Clear all diagnostic flags

DIA.OVERLOAD

Query cell overload error

SCs.DIA.OVERLOAD

Set cell overload value

–100.00 – 100.00 (percent)

DIA.UNDERLOAD

Query cell underload error

SCs.DIA.UNDERLOAD

Set cell underload value

–100.00 – 100.00 (percent)

DIA.ZREF

Query zero reference error

SCs.DIA.ZREF

Enable zero reference diagnostic

OFF, ON

SCs.DIA.ZREF.RANGE

Set zero reference range

0.00 – 100.00 (percent)

SCs.DIA.ZREF.THRESH

Set zero reference threshold

–100.00 – 100.00 (percent)

SCs.DIA.ZREF.TIME

Set zero reference timer

1 – 60 (seconds)

DIA.DRIFT

Query cell drift error

SCs.DIA.DRIFT

Enable cell drift diagnostic

OFF, ON

SCs.DIA.DRIFT.RANGE

Set cell drift range

0.00 – 100.00 (percent)

SCs.DIA.DRIFT.THRESH

Set cell drift threshold

0.00 – 100.00 (percent)

SCs.DIA.DRIFT.TIME

Set cell drift timer

1 – 300 (seconds)

DIA.SDALL

Returns real-time load cell noise (in counts)

DIA.NOISE

Enable peak-to-peak noise diagnostic

OFF, ON

DIA.NOISE.THRESH

Set peak-to-peak noise threshold for all scales

0.01 – 1000 (microvolts)

DIA.NOISE.TIME

Set peak-to-peak noise timer

1 – 300 (seconds)

DIA.UNBAL

Query unbalanced load error

SCs.DIA.UNBAL

Enable unbalanced load diagnostic

OFF, ON

SCs.DIA.UNBAL.RANGE

Set unbalanced load range

5 – 75 (percent)

SCs.DIA.UNBAL.THRESH

Set unbalanced load threshold

0 – 50 (percent)

Table 5-11.

iQUBE

2

Diagnostic Commands