Chapter 2

Specifications and Features

• • • • • •

Chapter 2 provides specifications for HI 6600 series instruments. The specifications listed are designed to assist in the
installation, operation and troubleshooting of your instrument. All service personnel should be familiar with this section
before installing or repairing the instrument.

Basic Specifications

HI 6610 Weight Processing Module (WPM)

Number of Channels
Each Weight Processing Module is a single channel of weight. HI 6600 Modular Sensor System can support up to 30
channels. The actual number of channels that can be transmitted by a single I/O table request depends on the PLC
interface format.

 EtherNet/IP:

Up to 30 Channels per request

 Modbus-TCP: Up to 14 Channels per request
 Modbus-RTU: Up to 14 Channels per request
 Profibus-DP:

Up to 10 Channels per request

Update Rate per Weight Processing Module (WPM)

 110 times per second per channel (processed weight, display, communications)

Weight Processing Module (WPM) Resolution

 Displayed - 1:10,000
 Internal - 1:8,388,608

WAVERSAVER

®

 User Selectable

OFF, 7.50 Hz, 3.50 Hz, 1.00 Hz (default), 0.50 Hz, 0.25 Hz

Averages

 1 to 250
 User-selectable in Single Increments

Load Sensor Input per WPM

 Up to four 350-ohm full Wheatstone bridge, strain gauge load sensor/cells (5 volt excitation) can be connected

to the weigh scale input on each WPM.