NOTE

Profibus Node Address #5 is the lowest number that can be used by a slave device.

2) Select termination drop down and select termination condition. Termination maybe be set to Enable,

Disable or Link. Link means that the termination is set on or off depending on whether pin 2 of the
connector is low (on) or high (off). There is an internal pull up on pin 2 that will set the termination off if
nothing is connected to it.

3) Click Save Parameters to save the entry.

4) You can also read the communication status of the instrument.

5) Click Home to return to the Home Page.

Initialization Process

To be able to add an HI 6600 to a Profibus-DP network, you need a PC or a PLC and software such as
Siemens Step 7™, Simatic Manager or the equivalent. The software must allow the Profibus-DP PLC and
the HI 6600 to exchange data.