Wiring protective earth ground, Caution – Wavetronix SmartSensor Matrix (SS-225) - User Guide User Manual

Page 108

Advertising
background image

APPENDIX

107

Caution

An authorized electrical technician should install the preassembled backplate. Per-
sons other than authorized and approved electrical technicians should NOT attempt
to connect the backplate to a power supply and/or traffic control cabinet, as there is a
serious risk of electrical shock through unsafe handling of the power source. Extreme
caution should be used when connecting the backplate to an active power supply.

The AC power conversion section of the backplate will come pre-wired as shown in Figure

D.3. The main three components of the AC power conversion section include:

˽

Click 201/202/204 AC to DC converter – A Click 201 provides 1 A of power and is ca-

pable of powering a single sensor; a Click 202 provides 2 A and can power two sensors;

a Click 204 provides 4 A and can power four sensors.

˽

Click 210 circuit breaker – Interrupts power during overload conditions and provides

a convenient way to turn power on and off for the entire system.

˽

Click 230 AC surge protector – Helps protect equipment from current surges on the

power lines.

Figure D.3 – AC Power Conversion

Wiring Protective Earth Ground

All connections are surge protected when the protective earth ground is wired to the PE

terminal block on the backplate. Normally, the backplate should be mounted to the chassis

of the cabinet to provide a ground path. It is strongly recommended that you provide a low

impedance protective earth connection.

Advertising