CHAPTER 3 • CONTACT CLOSURE COMMUNICATION

35

Detection

Channel

Menu Level 2

Menu Level 1

Mode Switch

Figure 3.7 – Click 112/114 Menu

Normally, SmartSensor Matrix will send 10 contact closure messages each second. If a rack

card does not receive communications from a sensor within 10 seconds, the rack card will

go into fail-safe mode and all of the contact closures will be activated and the corresponding

detection channel LEDs on the faceplate will turn on.

Attaching and Programming the Click 104

Use the following steps to set up the DIN rail contact closure module for each sensor:
1 Mount the Click 104 on a DIN rail over a T-bus connector. This connects the device’s

control bus (bus 2) to the installation’s shared communication bus; you can connect

your computer to another device on this shared bus, such as the Click 305 USB con-

verter, to access the Click 104 to configure it using Click Supervisor. Mounting the

Click 104 on the T-bus also connects it to the power source.

Figure 3.8 – Wiring the Click 104 Module

2 Send detection data to the data bus (bus 1). Connect a Click 222 to the Click 104 by

connecting jumper cables from the RJ-11 jacks on the faceplate of the Click 222 to the

RJ-11 jacks on the faceplate of the Click 104 (see Figure 3.8).