Clearing alarm history (fn006), Clearing alarm h – Yaskawa Junma Series SERVOPACK User Manual

Page 63

Advertising
background image

5.8 Utility Functions

E-62

„

Clearing Alarm History (Fn006)

The clear alarm history function deletes all of the alarm history recorded in the SERVOPACK.

Note: The alarm history is not deleted when the alarm reset is executed or the main circuit power

supply of the SERVOPACK is turned OFF.

Preparation

There are no tasks that must be performed before clearing the alarm history.

Operating Procedure

Use the following procedure.

Step

Display after Operation

Keys

Operation

1

Press the

Key to open the Utility

Function Mode main menu, and select

Fn006 using the

or

Key.

2

Press the

Key.

The display is switched to the execution
display of Fn006 (Clearing Alarm
History).

3

or

Press the

Key to clear the alarm

history.
During clearing, “Done” is displayed in
the status display. After the clearing is
completed, “BB” is displayed.

Note: Press the

Key not to clear

the alarm history. The display
returns to the Utility Function Mode
main menu.

B B

− F U N C T I O N −

F n 0 0 3

F n 0 0 6

F n 0 1 0

F n 0 1 2

B B

A l a r m H i s t o r y

S t a r t : [ D A T A ]
R e t u r n : [ S E T ]

D a t a C l e a r

B B

A l a r m H i s t o r y

S t a r t : [ D A T A ]

R e t u r n : [ S E T ]

D a t a C l e a r