1 connecting the digital input/output – KACO Powador XP200-HV TL User Manual

Page 27

Advertising
background image

Installation

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Page 27

Electrician

7.6.1 Connecting the digital input/output

-UDIO

1b 2b 3b 4b 5b

1a 2a 3a 4a 5a

230 V P

230 V N

Terminal

number

Terminal

designation

Specification

Wire cross- section,

max.

1a

UDI1 N

Potential-free

input contact,

max. 27 V, 27 mA

AWG 20

(0.75 mm

2

)

1b

UDI1 P

Figure 18: UDIO connection

Table 7:

Connections for digital input

7.6.1.1

S0 input

-UDIO

24 V

1b 2b 3b 4b 5b

1a 2a 3a 4a 5a

Signal transceiver

Current limiting

resistor, 4.7 kΩ

GND

Terminal

number

Terminal

designation

Specification

Wire cross- section,

max.

2a

S0

in

N

Max. 27 V,

27 mA

AWG 20

(0.75 mm

2

)

2b

S0

in

P

Figure 19: Connection for S0 input

Table 8:

Connections for S0 input