User interface

Page 58

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Parameter

Unit

Range

Description

Factory settings

Asynchronous Fault

Count

0 ... 100

Reserved parameter

10

Asynchronous Fault

Enable

0 ... 1

Reserved parameter

0

Grid Positive

Sequence

0

999.9

Positive sequence value of grid

0

COSPHI Control

Mode

0 ... 5

Reactive power supply method in

internal mode and RPC mode

0: disabled

1: fixed P

2: fixed cosφ

3: fixed Q

4: cosφ(P/Pn)

5: Q(U)

0

COSPHI Internal

Power Factor

–0.999 ... 1

Power factor reference in internal

mode

1

COSPHI Internal

Reactive Power

%

–99.9 ... 99.9

Reactive power reference in internal

mode (percent for rated one)

0

COSPHI Actual

Power Factor

–0.999 ... 1

Actual power factor value that is

applied (read only)

1

COSPHI RPC Power

Factor

–0.999 ... 1

Power factor reference in RPC mode

1

COSPHI RPC Reac-

tive Power

%

–99.9 ... 99.9

Reactive power reference in RPC

mode (percent for rated one)

0

COSPHI Stray Ratio

0 ... 2

Setup value for COSPHI control

Device-specific

Positive Sequence

PLL Enable

On(1), Off(0)

Usage of grid voltage of positive

sequence at PLL

1

FRT K Factor

0 ... 10

Setup constant during FRT control

2

FRT IQ Ramp

ms

0 ... 99999

Time to change the current from 0 A

to rated current. This time determines

the slope of the active current after

grid fault detection.

4000

FRT IQ Ramp Time

ms

0 ... 99999

Total time that the FRT IQ ramp func-

tion is activated

2000

FRT Overcurrent

Protection Time

ms

0 ... 99999

Time that the inverter is stopped after

grid fault clearance

200

Positive Sequence

LPF

Hz

0 ... 100

Cut-off frequency for RMS value of

positive sequence

100

PLL Freq LPF

Hz

0 ... 100

Cut-off frequency for frequency value

detection of PLL

100

Q(V) Control Target

Voltage

V

208 ... 440

Value of Q(V) Control Target Voltage

Device-specific

Q(V) Control K

Factor

0 ... 50

Setup constant for voltage control of

BDEW

3.1