KACO Powador XP200-HV TL User Manual

Page 85

Advertising
background image

Faults and Warnings

Operating Instructions Powador XP200-HV TL, XP250-HV TL, XP350-HV TL_EN

Page 85

Message

Code

Description

Grid Over Frequency

F32

Overfrequency on the grid side

Grid Under Frequency

F33

Underfrequency on the grid side

Grid CB Trip

F34

CB20 (grid circuit breaker) was tripped during operation

Parameters Version Error

F40

Version difference between the internal parameter table and the

program parameter table

Flash Memory Failure

F41

The flash memory used for programming the DSP C6000 on the

control board has failed.

FPGA Failure

F42

FPGA failure in XCU (main control) board

DSP28x Failure

F43

DSP F2000 on the control board has failed

ADC Failure

F44

The analog-digital converter on the control board has failed

NVSRAM Failure

F45

NVSRAM on the XCU (main control) board has failed.

ASYNC Failure

F46

ASYNC Warning (W31) has been repeated more than 10 times

CAN Failure

F47

CAN communication failure in the CAN network

MC22 Failure

F49

MC22 failed.

Emergency Stop

F50

The emergency stop (OFF switch) was pressed.

Cabinet Over Temp.

F51

Cabinet temperature > 55°C

MMI-XCU Communication Error

F63

Communication failure between MMI and XCU board

Table 32: Fault