5 thr, Ed figure 8-3, Figure 8-3. fault 1, open thermocouple -5 – Emerson OXYMITTER 4000 User Manual

Page 109: Oxymitter 4000, Alarms o2 t/c open, Instruction manual

Advertising
background image

Instruction Manual

IB-106-340 Rev. 3.0

December 2003

Rosemount Analytical Inc. A Division of Emerson Process Management

Troubleshooting 8-5

Oxymitter 4000

Alarms

O2 T/C Open

LOI

KEYPAD

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON

37260019

Figure 8-3. Fault 1, Open Thermocouple

a. Fault 1, Open Thermocouple

Figure 8-3 shows the electronic assembly
for an Oxymitter 4000 with a membrane
keypad (upper view) and an Oxymitter 4000
with an LOI (lower view). The upper view
also shows J1 and test points TP1 through
TP6, located on the microprocessor board,
below the membrane keypad or the LOI
module.

Membrane Keypad. When Fault 1 is de-
tected, the HEATER T/C LED flashes once,
pauses for three seconds, and repeats.

1. Check connector J1. Ensure the con-

nector is properly seated.

2. Using a multimeter, measure TP3+ to

TP4-. If the reading is 1.2 VDC ±0.1
VDC, the thermocouple is open.

3. Remove power. Disconnect J1. Meas-

ure continuity across the red and yel-
low thermocouple leads.

4. The measurement should read ap-

proximately 1 ohm.

5. If the thermocouple is open, see para-

graph 9-4h, Heater Strut Replacement.

LOI. When Fault 1 is detected, the LOI dis-
plays the “O2 T/C Open” message.

1. Remove power. Unscrew and remove

the LOI module from the electronic as-
sembly.

2. Reconnect power to the Oxymitter

4000.

3. Perform the diagnostic steps 1 through

5 shown for the membrane keypad.

Advertising