Figure 7-1. signal line connections, 250 ohms load resistance -0, Section 7 – Emerson OXYMITTER 4000 User Manual

Page 96: Oxymitter 4000, Instruction manual

Advertising
background image

Instruction Manual

IB-106-340 Rev. 3.0
December 2003

7-0 HART/AMS

Rosemount Analytical Inc. A Division of Emerson Process Management

Oxymitter 4000

SECTION 7

LOOP CONNECTORS

USE INTERFACE
00275 0013 ONLY

SERIAL PORT & BATTERY
CHARGER MUST
NOT BE USED IN
HAZARDOUS AREAS

SERIAL PORT

AC L1

AC N

+

+

-

-

4-20

TERMINAL BLOCK

LOOP CONNECTORS

4-20 mA SIGNAL LINE

HART

COMMUNICATOR

RL

250

ANALOG OUTPUT DEVICE

LEAD SET

HART COMMUNICATOR

REAR PANEL

23230001

Figure 7-1. Signal Line Connections,

≥≥≥≥ 250 Ohms Load Resistance

LOOP CONNECTORS

USE INTERFACE
00275 0013 ONLY

SERIAL PORT & BATTERY
CHARGER MUST
NOT BE USED IN
HAZARDOUS AREAS

SERIAL PORT

AC L1

AC N

+

+

-

-

4-20

TERMINAL BLOCK

LOOP CONNECTORS

4-20 mA SIGNAL LINE

HART

COMMUNICATOR

RL < 250

ANALOG OUTPUT DEVICE

250 OHM

LOAD

RESISTOR

(NOTE)

HART COMMUNICATOR

REAR PANEL

NOTE: THE SIGNAL LOOP MUST BE BROKEN

TO INSERT THE OPTIONAL 250 OHM
LOAD RESISTOR.

23230002

Figure 7-2. Signal Line Connections, < 250 Ohms Load Resistance