Instruction Manual

IB-106-340 Rev. 3.0
December 2003

3-4 Configuration with Keypad

Rosemount Analytical Inc. A Division of Emerson Process Management

Oxymitter 4000

3-2

LOGIC I/O

This two-terminal logic contact can be config-
ured either as a solid-state relay-activated alarm
or as a bi-directional calibration handshake sig-
nal to an IMPS 4000 or SPS 4000. The configu-
ration of this signal depends on the setting of
the LOGIC I/O PIN MODE via HART/AMS or
LOI. The ten different modes available are ex-
plained in Table 3-1.

a. Alarm

When configured as an alarm, this signal
alerts you to an out-of-spec condition. The
output is 5 V in series with a 340 ohm re-
sistor. For optimum performance, Rose-
mount recommends connecting the output
to a Potter & Brumfield 3.2 mA DC relay
(P/N R10S-E1Y1-J1.0K).

Of the ten modes in Table 3-1, mode 1
through mode 7 are the alarm modes. The
factory default is mode 5 for Oxymitter 4000
units without an IMPS 4000 or SPS 4000. In
this mode, the output will signal when a unit
alarm or a CALIBRATION RECOM-
MENDED indication occurs.

b. Calibration Handshake Signal

If using an optional IMPS 4000 or SPS
4000, the logic I/O must be configured for
calibration handshaking. Of the ten modes
in Table 3-1, only modes 8 and 9 are con-
figured for calibration handshaking. For an
Oxymitter 4000 with an IMPS 4000 or an
SPS 4000, the factory sets the default to
mode 8. In this mode, the logic I/O will be
used to communicate between the Oxymit-
ter 4000 and sequencer and to signal the
sequencer when a CALIBRATION REC-
OMMENDATION indication occurs.

Table 3-1. Logic I/O Configuration (as set at HART/AMS or LOI)

Mode

Configuration

0

The unit is not configured for any alarm condition.

1

The unit is configured for a Unit Alarm.

2

The unit is configured for Low O

2

.

3

The unit is configured for both a Unit Alarm and Low O

2

.

4

The unit is configured for a High AC Impedance/CALIBRATION RECOMMENDED.

5*

The unit is configured for both a Unit Alarm and a High AC Impedance/
CALIBRATION RECOMMENDED.

6

The unit is configured for both a Low O

2

and High AC Impedance/CALIBRATION

RECOMMENDED.

7

The unit is configured for a Unit Alarm, a Low O

2

, and a High AC Impedance/

CALIBRATION RECOMMENDED.

8**

The unit is configured for a calibration handshake with IMPS 4000 or SPS 4000.
CALIBRATION RECOMMENDED will initiate the calibration cycle.

9

The unit is configured for a calibration handshake. CALIBRATION RECOM-
MENDED will not initiate the calibration cycle with the IMPS 4000 or SPS 4000.

*The default condition for an Oxymitter 4000 without an IMPS 4000 or SPS 4000.

**The default condition for an Oxymitter 4000 with an IMPS 4000 or SPS 4000.