PiN

WirE

circuit fuNctioN

J1-1

85

High temperature shutdown:
Shutdown occurs when Wire 85 is
grounded by contact closure in HTO

J1-2

86

Low oil pressure shutdown: Shutdown
occurs when Wire 86 is grounded by
loss of oil pressure to the LOP

J1-3

13

12 VDC source voltage for the circuit
board

J1-4

18

Ignition Shutdown: Circuit board
action grounds Wire 18 for ignition
shutdown.

J2-1

0

INTERNAL USE

J2-2

0

INTERNAL USE

J2-3

14

12 VDC output for engine run condi-
tion. Used for fuel solenoid.

J2-5

23

Switched to ground for transfer relay
operation

J2-6

NOT USED

PiN

WirE

circuit fuNctioN

J2-7

NOT USED

J2-8

15B

Provides an electrical connection for
charge current to reach the battery
from the battery charger. Provides
12VDC to the Transfer Relay

J2-9

NOT USED

J2-10

0

Common Ground

J2-11

56

12 VDC output to starter contactor for
single cylinder engines.

J2-15

NOT USED

J2-16

NOT USED

J2-17

NOT USED

J2-18

NOT USED

Wired Plug 1

N1

240 VAC sensing for control board.

Wired Plug 2

N2

240 VAC sensing for control board.

Page 98

8 kW J1 connector Pin Descriptions

J2

J1

J2 CONNECTOR

(HARNESS END)

N1/N2 CONNECTOR

(HARNESS END)

N1/N2 CONNECTOR

(PCB END)

10 11 12 13 14 15 16 17 18

1

2

3

4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

1

2

3

4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

1

2

3

4

1

2

3

4

5

6

7

8

9

J1 CONNECTOR

(HARNESS END)

J2 CONNECTOR

(PCB END)

J1 CONNECTOR

(PCB END)

1

2

Figure 4. 8 kW Printed Circuit Boards and J1 Connector

Part 4

DC CONTROL

sEctioN 4.1

DEscriPtioN aND comPoNENts

Advertising
This manual is related to the following products: