Troubleshooting flow charts part 3 – Generac Power Systems 8 kW LP User Manual

Page 75

Advertising
background image

REPLACE PRINTED

CIRCUIT BOARD

REPAIR OR REPLACE

REPLACE CHARGER

Problem 11 – No Battery Charge

“Pre-Wire Load Center”

TEST 40 – CHECK

BATTERY CHARGER

SUPPLY VOLTAGE

TEST 41 – CHECK

BATTERY CHARGER

OUTPUT VOLTAGE

TEST 42 – CHECK

WIRE 0/15B

GOOD

GOOD

BAD

REPAIR OR

REPLACE

BAD

BAD

NO BATTERY

SUPPLY VOLTAGE

REPLACE PRINTED

CIRCUIT BOARD

REPAIR OR REPLACE

REPLACE CHARGER

Problem 12 – No Battery Charge

“RTSN & RTSE Transfer Switch”

TEST 43 – CHECK

BATTERY CHARGER

SUPPLY VOLTAGE

TEST 44 – CHECK

BATTERY CHARGER

OUTPUT VOLTAGE

TEST 45 – CHECK

WIRE 0/15B

GOOD

GOOD

BAD

REPAIR OR

REPLACE

BAD

BAD

NO BATTERY

SUPPLY VOLTAGE

REPLACE PRINTED

CIRCUIT BOARD

REPAIR OR REPLACE

REPLACE CHARGER

Problem 13 – No Battery Charge

“GenReady Load Center”

TEST 46 – CHECK

BATTERY CHARGER

SUPPLY VOLTAGE

TEST 47 – CHECK

BATTERY CHARGER

OUTPUT VOLTAGE

TEST 48 – CHECK

WIRE 0/15B

GOOD

GOOD

BAD

REPAIR OR

REPLACE

BAD

BAD

NO BATTERY

SUPPLY VOLTAGE

REPLACE PRINTED

CIRCUIT BOARD

REPAIR OR REPLACE

REPLACE CHARGER

Problem 14 – No Battery Charge

“Load Shed Transfer Switch”

TEST 49 – CHECK

BATTERY CHARGER

SUPPLY VOLTAGE

TEST 50 – CHECK

BATTERY CHARGER

OUTPUT VOLTAGE

TEST 51 – CHECK

WIRE 0/15B

GOOD

GOOD

BAD

REPAIR OR

REPLACE

BAD

BAD

NO BATTERY

SUPPLY VOLTAGE

Page 73

TRANSFER SWITCH

sEctioN 3.3

trouBlEsHootiNG floW cHarts

Part 3