Part 4, Description and components – Generac Power Systems 8 kW LP User Manual

Page 102

Advertising
background image

Page 100

J2

J3

(STEPPER MOTOR)

REMOTE WIRELESS CONNECTION

J1

J2 CONNECTOR

(HARNESS END)

10 11 12 13 14 15 16 17 18

1

2

3

4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

1

2

3

4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

1

2

3

4

1

2

3

4

5

6

7

8

9

J1 CONNECTOR

(HARNESS END)

J2 CONNECTOR

(PCB END)

J1 CONNECTOR

(PCB END)

N1/N2 CONNECTOR

(HARNESS END)

N1/N2 CONNECTOR

(PCB END)

1

2

PiN

WirE

circuit fuNctioN

J1-1

85

High temperature shutdown:
Shutdown occurs when Wire 85 is
grounded by contact closure in HTO

J1-2

86

Low oil pressure shutdown: Shutdown
occurs when Wire 86 is grounded by
loss of oil pressure to the LOP

J1-3

13

12 VDC source voltage for the circuit
board

J1-4

18

Ignition Shutdown: Circuit board
action grounds Wire 18 for ignition
shutdown.

J2-1

INTERNAL USE ONLY

J2-2

INTERNAL USE ONLY

J2-3

14

12 VDC output for engine run condi-
tion. Used for fuel solenoid and choke
solenoid operation.

J2-4

817

Grounded by printed circuit board to
turn on System Ready (Green) LED.

J2-5

23

Switched to ground for transfer relay
operation

J2-6

NOT USED

J2-7

NOT USED

PiN

WirE

circuit fuNctioN

J2-8

15B

Provides an electrical connection for
charge current to reach the battery
from the battery charger. Provides 12
VDC to the Transfer Relay

J2-9

820

Positive voltage (+5 VDC) for status
LEDs.

J2-10

0

Common Ground

J2-11

56

12 VDC output to starter contactor
relay for V-Twin engines

J2-12

NOT USED

J2-13

818

Grounded by board to turn on the
Alarm (Red) LED.

J2-14

NOT USED

J2-15

90

Switched to ground for choke sole-
noid operation

J2-16

INTERNAL USE ONLY

J2-17

NOT USED

J2-18

NOT USED

J3

Control wires for Stepper Motor

Wired Plug-1

N1

240 VAC sensing for control board.

Wired Plug-2

N2

240 VAC sensing for control board.

12/14 kW J1 connector Pin Descriptions

Figure 6. 12/14 kW Printed Circuit Board and J1 Connector

Part 4

DC CONTROL

sEctioN 4.1

DEscriPtioN aND comPoNENts

Advertising