Visual inspection, Insulation resistance, The megohmmeter – Generac Power Systems 8 kW LP User Manual
Page 24
Part 1
ViSual inSpection
When it becomes necessary to test or troubleshoot a 
generator, it is a good practice to complete a thorough 
visual inspection. Remove the access covers and look 
closely for any obvious problems. Look for the following:
• Burned or broken wires, broken wire connectors,
damaged mounting brackets, etc.
• Loose or frayed wiring insulation, loose or dirty
connections.
•	 Check	that	all	wiring	is	well	clear	of	rotating	parts.
•	 Verify	that	the	Generator	properly	connected	for	the	
correct rated voltage. This is especially important on 
new installations. See Section 1.2, “AC Connection 
Systems”.
• Look for foreign objects, loose nuts, bolts and other
fasteners.
• Clean the area around the Generator. Clear away
paper, leaves, snow, and other objects that might 
blow against the generator and obstruct its air 
openings.
inSulation reSiStance
The insulation resistance of stator and rotor windings 
is a measurement of the integrity of the insulating 
materials that separate the electrical windings from 
the generator steel core. This resistance can degrade 
over time or due to such contaminants as dust, dirt, 
oil, grease and especially moisture. In most cases, 
failures of stator and rotor windings is due to a break-
down in the insulation. And, in many cases, a low insu-
lation resistance is caused by moisture that collects 
while the generator is shut down. When problems are 
caused by moisture buildup on the windings, they can 
usually be corrected by drying the windings. Cleaning 
and drying the windings can usually eliminate dirt and 
moisture built up in the generator windings.
the meGohmmeter
GENERAL:
A megohmmeter, often called a “megger”, consists of 
a meter calibrated in megohms and a power supply. 
Use a power supply of 500 volts when testing stators 
or rotors. DO NOT APPLY VOLTAGE LONGER THAN 
ONE (1) SECOND.
TESTING STATOR INSULATION:
All parts that might be damaged by the high meg-
ger voltages must be disconnected before testing. 
Isolate all stator leads (Figure 8) and connect all of 
the stator leads together. FOLLOW THE MEGGER 
MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 500 volts. Connect 
one megger test lead to the junction of all stator 
leads, the other test lead to frame ground on the sta-
tor can. Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators 
may be calculated using the following formula:
MINIMUM INSULATION
GENERATOR RATED VOLTS
RESISTANCE
=
__________________________
+1
(in “Megohms”)
1000
eXample: Generator is rated at 120 volts ac. 
divide “120” by “1000” to obtain “0.12”. then add 
“1” to obtain “1.12” megohms. minimum insulation 
resistance for a 120 Vac stator is 1.12 megohms.
If the stator insulation resistance is less than the cal-
culated minimum resistance, clean and dry the stator. 
Then, repeat the test. If resistance is still low, replace 
the stator.
Use the Megger to test for shorts between isolated 
windings as outlined “Stator Insulation Tests”.
Also test between parallel windings. See “Test 
Between Windings” on next page.
TESTING ROTOR INSULATION (12-20kW):
Apply a voltage of 500 volts across the rotor posi-
tive (+) slip ring (nearest the rotor bearing), and 
a clean frame ground (i.e. the rotor shaft). DO 
NOT EXCEED 500 VOLTS AND DO NOT APPLY 
VOLTAGE LONGER THAN 1 SECOND. FOLLOW 
THE MEGGER MANUFACTURER’S INSTRUCTIONS 
CAREFULLY.
rotor miNimum iNsulatioN rEsistaNcE:
1.5 megohms
TESTING ROTOR INSULATION (8-10kW):
No test available.
*
cautioN: Before attempting to measure insu-
lation resistance, first disconnect and isolate 
all leads of the winding to be tested. Electronic 
components, diodes, surge protectors, relays, 
voltage regulators, etc., can be destroyed if 
subjected to high megger voltages.
Figure 7. One Type of Hi-Pot Tester
Page 22
GENERAL INFORMATION
sEctioN 1.5
tEstiNG, clEaNiNG aND DrYiNG