Test 74 – check and adjustignition magnetos – Generac Power Systems 8 kW LP User Manual

Page 140

Advertising
background image

Page 138

WIRE 18 CONNECTION

Figure 32. Wire 18 Connection 10-20 kW Units

2. Depending on engine type, do the following:

a. On V-twin units, remove Wire 56 from the

Starter Contactor Relay (SCR). Using a jumper
lead, jump 12 VDC from Wire 15B at TB1
(Customer Connection) to the terminal on the
SCR from which Wire 56 was removed. The
generator will start cranking. As it is cranking,
repeat Test 70. Reconnect Wire 56 when done.

b. On single cylinder units, connect a jumper lead

from the stud to which Wire 56 is connected
on the Starter Contactor (SC) and 12 VDC
Wire 15B at TB1 (Customer Connection). The
generator will start cranking. As it is cranking,
repeat Test 70.

WIRE 18
CONNECTION

Figure 33. Wire 18 Connection 8 kW Units

3. If spark now occurs with Wire 18 removed, check for

a short to ground. Remove the J1 Connector from the

circuit board.

4. Set a VOM to measure resistance. Connect one test lead

to Wire 18 (disconnected in Step 1). Connect the other

test lead to a clean frame ground. INFINITY should be

measured.

5. Reconnect the J1 Connector to the circuit board.

RESULTS:

1. If INFINITY was not measured in Step 4, repair or replace

shorted ground Wire 18 between the J1 Connector from

the circuit board to the stud or bullet connector.

2. If INFINITY was measured in Step 4, replace the circuit

board and retest for spark.

3. If ignition spark still has not occurred, proceed to Test 74.

teSt 74 – check and adjuSt iGnition

maGnetoS

DISCUSSION:
In Test 70, a spark tester was used to check for
engine ignition. If sparking or weak spark occurred,
one possible cause might be the ignition magneto(s).
This test consists of checking ohm values across the
primary and secondary windings of the magneto and
adjusting the air gap between the ignition magneto(s)
and the flywheel. The flywheel and flywheel key will
also be checked during this test. A diode is installed
before the primary winding inside the coil. This is
done to inhibit a spark occurring on both magnetos at
the same time.

PROCEDURE: TESTING MAGNETOS V-TWIN ONLY

1. Disconnect the J1 connector from the printed circuit

board.

2. Disconnect spark plug wires from the spark plugs on

cylinder one and two.

3. Set VOM to measure resistance.
4. Connect the positive

(red) meter lead to the bolt connec-

tor where Wire 18 was disconnected in Step 1. Connect

the negative

(black) meter lead to a clean frame ground.

A resistance of approximately 300K ±10K ohms should

be measured. This reading is the primary winding of

both coils in parallel.

5. Connect the positive meter lead to the spark plug

wire and connect the negative meter lead to a clean

frame ground. Approximately 14K ±3 ohms should be

measured. This reading is the secondary winding of

both coils in parallel. If INFINITY, or a low or high ohm

reading is measured, replace the magnetos.

6. Connect the negative (black) meter lead to the bolt

connector where Wire 18 was disconnected in Step 1.

Connect the positive (red) meter lead to the spark plug

wire on cylinder number two. The meter should indicate

INFINITY. This step is testing the diodes in both magnetos

to ensure they are still functioning.

7. Repeat Step 6 on cylinder two. If INFINITY is not

measured, replace the magnetos.

note: it is recommended to replace magnetos
in pairs.

Part 4

DC CONTROL

sEctioN 4.4

DiaGNostic tEsts