Part 3, Troubleshooting flow charts – Generac Power Systems 8 kW LP User Manual

Page 74

Advertising
background image

REPLACE

CIRCUIT

BOARD

CORRECT

UTILITY

SOURCE

VOLTAGE

REPLACE

GO TO PROBLEM 7

REPAIR OR

REPLACE

WIRING

REPAIR OR REPLACE WIRE

N1A/N2A BETWEEN N1/N2
LUGS AND FUSE HOLDER

REPAIR N1/N2 OPEN WIRING

BETWEEN TRANSFER

SWITCH AND GENERATOR

Problem 10 – Unit Starts and Transfer Occurs When Utility Power Is On

8 kW: Green LED Flashes

10-20 kW: Status – Utility Lost

TEST 37 – CHECK
UTILITY SENSING

VOLTAGE AT

CIRCUIT BOARD

TEST 36 –

CHECK N1 & N2

VOLTAGE

TEST 38 – CHECK

UTILITY SENSE

VOLTAGE

TEST 39 –

CHECK VOLTAGE

AT TERMINAL

LUGS N1 & N2

TEST 34 –

CHECK FUSE

F1 & F2

GOOD

GOOD

GOOD

GOOD

GOOD

BAD

BAD

BAD

BAD

BAD

Page 72

Part 3

TRANSFER SWITCH

sEctioN 3.3

trouBlEsHootiNG floW cHarts