1 description and components, General, Terminal strip / interconnection terminal – Generac Power Systems 8 kW LP User Manual

Page 98: Circuit board, Auto-off-manual switch

Advertising
background image

General

This section will familiarize the reader with the various
components that make up the DC control system.
Major DC control system components that will be
covered include the following:

• A Terminal Strip / Interconnection Terminal
• A Circuit Board.
• An AUTO-OFF-MANUAL Switch.
• A 7.5 Amp Fuse.

terminal Strip / interconnection

terminal

The terminals of this terminal strip are connected to
identically numbered terminals on a transfer switch
terminal board. The terminal board connects the
transfer switch to the circuit board.
The terminal board provides the following connection
points:

A. UTILITY 1 and UTILITY 2

1. Connect to identically marked terminals on a

transfer switch terminal board.

B. 23 and 15B

1. Connect to identically numbered terminals on

the terminal board of the transfer switch.

2. This circuit connects the circuit board to the

transfer relay coil in the transfer switch.

TERMINAL STRIP

0

N1 N2

15B 23

Figure 1. Terminal Strip

circuit Board

The circuit board controls all standby electric system
operations including (a) engine startup, (b) engine
running, (c) automatic transfer, (d) automatic retrans-
fer, and (e) engine shutdown. In addition, the circuit
board performs the following functions:

• Delivers “field boost” current to the generator rotor

windings (see “Field Boost Circuit” in Section 2.2).

• Starts and “exercises” the generator once every

seven days.

• Provides automatic engine shutdown in the event of

low oil pressure, high oil temperature, overspeed,
no RPM sense, overcrank, or low battery.

An 18-pin and a 4-pin connector are used to inter-
connect the circuit board with the various circuits of
the DC systems. Connector pin numbers, associated
wires and circuit functions are listed in the CHART on
the next page.
If the Utility sensing voltage drops below a preset
value, circuit board action will initiate automatic
generator star tup and transfer to the “Standby”
source side.
The crank relay and fuel solenoid valve are energized
by circuit board action at the same time.

DIGITAL INPUT/OUTPUT FUNCTIONS:

Postion

Digital inputs

Digital outputs

1

Low Oil Pressure

Not Used

2

High Temperature

Not Used

3

Internal Use

Not Used

4

Internal Use

Not Used

5

Internal Use

Fuel

6

Not Used

Starter

7

Auto

Ignition

8

Manual

Transfer

*

DaNGEr: tHE GENErator ENGiNE Will

craNK aND start WHEN tHE 7-DaY
EXErcisEr sWitcH is actuatED. tHE uNit
Will also craNK aND start EVErY 7
DaYs tHErEaftEr, oN tHE DaY aND at tHE
timE of DaY tHE sWitcH Was actuatED.

auto-oFF-manual SWitch

This 3-position switch permits the operator to (a)
select fully automatic operation, (b) start the generator
manually, or (c) stop the engine and prevent automatic
startup. Switch terminals are shown pictorially and
schematically in Figure 6, below.

Page 96

Part 4

DC CONTROL

sEctioN 4.1