Generator

Unit

8 kW

10 kW

12 kW

14 kW

16 kW

17 kW

20 kW

Rated Max. Continuous
Power Capacity (Watts*)

7,000 NG

8,000 LP

9,000 NG

10,000 LP

12,000 NG

12,000 LP

13,000 NG

14,000 LP

16,000 NG

16,000 LP

16,000 NG

17,000 LP

18,000 NG

20,000 LP

Rated Voltage

120/240

Rated Voltage at No-Load
(NG)

220-235

247-249

Rated Max. Continuous Load
Current (Amps)
120 Volts** (NG/LP)
240 Volts (NG/LP)

58.3/66.6
29.2/33.3

75.0/83.3
37.5/41.6

100.0/100.0

50.0/50.0

108.3/116.6

54.2/58.3

133.3/133.3

66.6/66.6

133.3/141.6

66.6/70.8

150.0/166.6

75.0/83.3

Main Line Circuit Breaker

35 Amp

45 Amp

50 Amp

60 Amp

65 Amp

65 Amp

100 Amp

Circuits*** 50A, 240V

-

-

-

1

1

1

-

40A, 240V

-

-

1

1

1

1

-

30A, 240V

1

1

1

-

-

-

-

20A, 240V

-

1

-

1

1

1

-

20A, 120V

1

3

3

4

5

5

-

15A, 120V

5

3

5

4

5

5

-

Phase

1

Number of Rotor Poles

2

Rated AC Frequency

60 Hz

Power Factor

1

Battery Requirement

Group 26R, 12

Volts and 350 CCA

Minimum

Group 26R, 12 Volts and 525 CCA Minimum

Weight (unit only in lbs.)

340

387

439

439

455

455/421

450

Enclosure

Steel

Steel

Steel

Steel

Steel

Steel/Aluminum

Aluminum

Normal Operating Range

-20° F (-28.8° C) to 77° F (25° C)

* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.

Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C (10 F) above 16 C (60 F)
ambient temperature.

** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits. The maximum current in each circuit must not exceed the value

stated for the 240 volts.

*** Circuits to be moved must be protected by same size breaker. For example, a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer switch.

Stator WindinG reSiStance ValueS / rotor reSiStance

8 kW

10 kW

12 kW

14 kW

16 kW

17 kW

20 kW

Power Winding: Across 11 & 22

0.123-0.1439

0.090-0.105

0.100-0.116

0.100-0.116

0.074-0.086

0.074-0.086

0.0415-0.0483

Power Winding: Across 33 & 44

0.123-0.1439

0.090-0.105

0.100-0.116

0.100-0.116

0.074-0.086

0.074-0.086

0.0415-0.0483

Excitation Winding: Across 2 & 6

0.776-0.902

0.511-0.594

0.876-1.018

0.876-1.018

0.780-0.906

0.780-0.906

0.731-0.850

Rotor Resistance

3.01-3.49

3.22-3.74

7.96-9.25

7.96-9.25

8.79-10.21

8.79-10.21

10.02-11.65

sPEcificatioNs