Test 76 – check high oiltemperature switch, Test 77 – check and adjust valves – Generac Power Systems 8 kW LP User Manual

Page 144

Advertising
background image

Page 142

a. Disconnect the J1 Connector from the printed

circuit board.

b. Connect one test lead to Wire 86 (disconnected

from LOP). Connect the other test lead to Pin
Location 4 (Wire 86) of the J1 Connector at the
Circuit Board (for all models). CONTINUITY
should be measured. If CONTINUITY is not
measured, repair or replace Wire 86 between
the LOP switch and the J1 Connector.

c. Connect one test lead to Wire 0 ( disconnected

from LOP). Connect the other test lead to a clean
frame ground. CONTINUITY should be measured.
If CONTINUITY is NOT measured repair or replace
Wire 0 between the LOP and the ground terminal
connection on the engine mount.

7. If the LOP switch tests good in Step 5 and oil pressure

is good in Step 4 but the unit still shuts down with a LOP

fault, check Wire 86 for a short to ground. Set a VOM to

measure resistance. Disconnect the J1 Connector from

the circuit board. Remove Wire 86 from the LOP switch.

Connect one test lead to Wire 86. Connect the other

test lead to a clean frame ground. INFINITY should be

measured. If CONTINUITY is measured, repair or replace

Wire 86 between the LOP switch and the J1 Connector.

RESULTS:

1. Replace switch if it fails the test.

teSt 76 – check hiGh oil temperature

SWitch

DISCUSSION:
If the temperature switch contacts have failed in a closed
position, the engine will fault out on “OVERTEMP”. If the
unit is in an overheated condition, the switch contacts will
close at 293° F. This will normally occur from inadequate
airflow through the generator.

PROCEDURE:

1. Verify that the engine has cooled down (engine block

is cool to the touch). This will allow the contacts in the

High Oil Temperature Switch to close.

2. Check the installation and area surrounding the generator.

There should be at least three feet of clear area around

the entire unit. Make sure that there are no obstructions

preventing incoming and outgoing air.

3. Disconnect Wire 85 and Wire 0 from the High Oil

Temperature Switch.

4. Set a VOM to measure resistance. Connect the test

leads across the switch terminals. The meter should

read INFINITY.

5. If the switch tested good in Step 4, and a true overtem-

perature condition has not occurred, check Wire 85 for a

short to ground. Remove J1 Connector from the circuit

board. Set the VOM to measure resistance. Connect

one test lead to Wire 85 (disconnected from High Oil

Temperature Switch). Connect the other test lead to a

clean frame ground. INFINITY should be measured.

TESTING HIGH OIL TEMPERATURE SWITCH:

6. Remove the High Oil Temperature Switch.
7. Immerse the sensing tip of the switch in oil as shown in

Figure 43, along with a suitable thermometer.

8. Set a VOM to measure resistance. Then, connect the

VOM test leads across the switch terminal and the

switch body. The meter should read INFINITY.

9. Heat the oil in the container. When the thermometer

reads approximately 283°-305° F. (139°-151° C.), the

VOM should indicate CONTINUITY.

Figure 43. Testing the Oil Temperature Switch

RESULTS:

1. If the switch fails Step 4, or Steps 8-9, replace the

switch.

2. If INFINITY was NOT measured in Step 5, repair or

replace Wire 85 between the Circuit Board and the High

Oil Temperature Switch.

teSt 77 – check and adjuSt ValVeS

DISCUSSION:
Improperly adjusted valves can cause various engine
related problems including, but not limited to, hard
starting, rough running and lack of power. The valve
adjustment procedure for both the single cylinder and
the V-twin engines is the same.