AC GENERATORS

sEctioN 2.3

trouBlEsHootiNG floWcHarts

Use the “Flow Charts” in conjunction with the detailed
instructions in Section 2.4. Test numbers used in
the flow charts correspond to the numbered tests in
Section 2.4.

The first step in using the flow charts is to correctly
identify the problem. Once that has been done, locate
the problem on the following pages. For best results,
perform all tests in the exact sequence shown in the
flow charts.

Part 2

Page 37

General

REPAIR

OR

REPLACE

REPAIR

OR

REPLACE

REPAIR

OR

REPLACE

THEN

RETEST

REPLACE

VOLTAGE

REGULATOR

TEST 1 - CHECK

MAIN CIRCUIT

BREAKER

TEST 4 - PERFORM

FIXED EXCITATION /

ROTOR AMP DRAW

PERFORM STATOR

INSULATION

RESISTANCE TEST

-

SECTION 1.4

PERFORM ROTOR

INSULATION

RESISTANCE TEST

-

SECTION 1.4

TEST 7 - TEST

STATOR

TEST 5 - WIRE

CONTINUITY

TEST 6 -

FIELD BOOST

TEST 11 -

CHECK
ROTOR

RESISTANCE

CHECK

VOM

FUSES

TEST 12 -

CHECK

BRUSHES &

SLIP RINGS

TEST 13 -

TEST ROTOR

ASSEMBLY

REPAIR

OR REPLACE

FUSES

RE-TEST

BAD

BAD

BAD

BAD

BAD

BAD

BAD

BAD

GOOD

GOOD

GOOD

GOOD

Problem 1 - Generator Produces Zero Voltage or Residual Voltage

(12-20 kW)

D

G

A

C

B

GOOD

GOOD

RESET TO

“ON”

OR REPLACE

IF BAD