TRANSFER SWITCH

sEctioN 3.3

trouBlEsHootiNG floW cHarts

Part 3

Page 71

Problem 8 – In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator

Shuts Down When Utility Returns But There Is No Retransfer To Utility Power

OR

Generator Transfers to Standby During Excercise or in Manual Mode

BAD

BAD

REPAIR OR REPLACE AS NEEDED

REPAIR OR REPLACE AS NEEDED

REPLACE

GOOD

GOOD

GOOD

TEST 27 – CHECK

MANUAL TRANSFER

SWITCH OPERATION

TEST 31 – CHECK

WIRE 23

BAD

TEST 32 – CHECK

UTILITY CONTROL

CIRCUIT

TEST 29 – TEST

TRANSFER

RELAY

BAD

REPAIR OR REPLACE MECHANISM

TEST 34 – CHECK

FUSE F1 & F2

TEST 35 – CHECK

N1 & N2 WIRING

GOOD

GOOD

BAD

BAD

REPAIR OR REPLACE

WIRING

INSPECT/REPLACE
PRINTED CIRCUIT BOARD

FINISH

Problem 9 – Blown F1 or F2 Fuse