GENERAL INFORMATION

sEctioN 1.3

NoN-PrEPacKaGED iNtErcoNNEctioNs

Part 1

connect a 2008 and later load center SWitch

to a pre-2008 air-cooled Generator.

PROCEDURE:

1. Follow all instructions located in the Installation Manual

that was supplied with the unit regarding mounting of the

switch, junction box, and generator.

note: When installing a standalone pre-2008 gen-
erator, the battery charger will be located in the
generator utilizing the 12 Vdc trickle charger.

2. Inside the Junction box between the generator and the

transfer switch there will be 4 wires coming from the

generator and 5 wires from the transfer switch.

3. Using the following diagram and UL approved wire nuts

connect the following wires together. Wire 0 will not be

utilized for this setup.

note: remove the battery charger from the trans-
fer switch; it will not be utilized in the operation of
the generator.

WIRE NUTS

N1 (BLU)

N2 (YEL)

23 (BRN)

194 (ORG)

N1 (YEL)

N2 (YEL)

23 (WHT)

15B (RED)

0 (BLK)

CONTROL WIRES FROM

ENGINE GENERATOR

CONTROL WIRES FROM

TRANSFER SWITCH

Figure 3. Wire Connections

WIRE
NUTS

N1 (BLU)

N2 (YEL)

23 (BRN)

194 (ORG)

N1 (YEL)

N2 (YEL)

23 (WHT)

15B (RED)

0 (BLK)

CONTROL WIRES FROM ENGINE GENERATOR

PRE “08” HSB AIR-COOLED GENERATORS

SINGLE & V-TWIN ENGINES

“08” & LATER LOAD CENTER

TRANSFER SWITCH

EXTERNAL CUSTOMER

CONNECTION BOX

CONTROL WIRES FROM TRANSFER SWITCH

Figure 4. Pre-2008 HSB Interconnections